Installing Custom Cable Systems
890 USE 100 00
227
D .7 Installing Connectors W ithout the Tool
If you are using the Modbus Plus connector installation tool
(ASMBPL001), do not follow the instructions below. Go to the
instructions in the previous part of this chapter, Installing
Connectors W ith the Tool .
If you are not using the installation tool, continue with the instructions
below.
D .7.1 Before You Start
Make sure you have the proper type of connector for each point on the
network cable:
Connector type ASMBKT185 (light grey) must be installed at the two
end points.
Two connectors are contained in the Modicon kit with this part number.
Connector type ASMBKT085 (dark grey) must be installed at each
inline point.
One connector is contained in the kit with this part number.
1 2 3 1 2 3
TERMINATING
CONNECTOR
ASMBKT185
INLINE
CONNECTOR
ASMBKT085
INSTALL AT
END POINTS
INSTALL AT
INLINE POINTS
(TWO PER KIT) (ONE PER KIT)
Figure 97 Modbus Plus Connectors
You will need the following tools: electrician’s knife; wire stripper;
small flatblade screwdriver; ohmmeter with a lowresistance range
(0200 ohms).
Vedere la pagina 238