Schneider Electric Modbus Plus Network Bridge Multiplexer none Guida di Installazione Pagina 52

  • Scaricare
  • Aggiungi ai miei manuali
  • Stampa
  • Pagina
    / 261
  • Indice
  • SEGNALIBRI
  • Valutato. / 5. Basato su recensioni clienti
Vedere la pagina 51
36 Introducing the Modbus Plus Network
890 USE 100 00
The types of devices used in your application determine how many
Modbus Plus networks you can join.
V You can address a programmable controller destination on a remote
network that is up to four networks away from the originating node
(that is, with four bridges in the message path).
V Hostbased network adapters can be addressed up to three
networks away (through three bridges).
V A single Modbus slave device at a Bridge Multiplexer port can also
be addressed up to three networks away. A slave device that is part
of a Modbus network at a Bridge Multiplexer port can be addressed
up to two networks away (through two bridges).
Vedere la pagina 51
1 2 ... 47 48 49 50 51 52 53 54 55 56 57 ... 260 261

Commenti su questo manuale

Nessun commento