Xantrex XW Solar Charge Controller Installation
4–12 975-0239-01-01
This manual for use by qualified personnel only
Wiring
DC Terminal Connector Locations
Terminal connectors for DC wiring are located inside the wiring compartment.
The labels above the DC wiring terminals and inside the wiring compartment
identify all the connection points. See Figure 4-8.
Wire Size and Over-current Protection Requirements
The wiring, over-current protection devices (fuses and circuit breakers),
and installation methods used must conform to all national and local
electrical code requirements.
Wiring must be protected from physical damage with conduit or a
strain relief clamp.
To preserve signal integrity on communication cables, the BTS, auxiliary output,
and network cables must pass through a different conduit than the conduits used
for PV and battery cables. You should pull the BTS cable through the conduit first
as the connector may not fit if other wires have been pulled first.
Important: Installations must meet all local electrical codes. Installations of this
equipment should only be performed by a qualified electrician or a Certified
Renewable Energy (RE) System Installer.
WARNING: Shock Hazard
Disconnect battery and PV sources before wiring.
Figure 4-8 DC Connection Terminals