Electrical Specifications
975-0239-01-01 A–3
This manual for use by qualified personnel only
Xantrex XW Series Overload Capability
Loads presented to the inverter are seldom constant. Typically, large loads are
operated for only short periods of time. In order to provide the maximum utility,
Schneider Electric inverters are allowed to operate at power levels that exceed
their continuous power ratings. This graph shows how loads that are larger than
the inverter can sustain continuously can be operated for useful periods of time.
The length of time that the inverter can operate at high power is limited by
temperature. When large loads are run, the inverter’s temperature increases.
At the point where more heat is created in the inverter than can be dissipated,
its ability to operate becomes time limited.
Maximum Output Fault Current
and Duration - Grid-Interactive
Mode
425 A peak
~0.4 ms
425 A peak
~0.4 ms
80 A peak
~25 ms
AC Output Breaker 60 A double-pole
AC Output Frequency 60.0 ±0.1 Hz
Total Harmonic Distortion < 5%
Automatic Transfer Relay 60 A
Auxiliary Relay Output 0–12 Vdc, maximum 250 mA DC
CEC Weighted Efficiency 92.5% 93.0% 91%
CEC Power Rating 5,752 W 4,453 W 4,039 W
DC Input Voltage (Nominal) 50.4 Vdc 50.4 Vdc 25.2 Vdc
DC Input Voltage Range 44–64 Vdc 44–64 Vdc 22–32 Vdc
DC Current at Rated Power 130 A 96 A 178 A
Continuous Charge Rate at
L-L voltage
100 A 85 A 150 A
Power Factor Corrected Charging PF (0.98)
a.This unit or system is provided with fixed trip limits and shall not be aggregated above 30 kW on a single Point of Common
Connection
Table A-1 Xantrex XW Power System Electrical Specifications
Model
Xantrex XW6048
120/240 60
Xantrex XW4548
120/240 60
Xantrex XW4024
120/240 60