Inverter/Charger Installation
2–18 975-0239-01-01
This manual for use by qualified personnel only
Making DC Connections
This section describes how to make DC connections between the inverter/
charger and the power distribution panel (using the pre-installed DC cables in
the distribution panel), between the distribution panel to the batteries
(using battery cables provided by the installer—see Table 2-2 on page 2–12).
This section also provides procedures for installing the battery temperature
sensor. See Appendix C, “Alternate System Configurations” if the installation will
not be including a Xantrex XW Power Distribution Panel.
To connect the Xantrex XW Power Distribution Panel to the inverter:
1. Connect the pre-installed DC cables from the Xantrex XW Power Distribution
Panel to the inverter DC terminals. Figure 2-12 shows the proper stacking
order of hardware. Be careful to observe proper polarity.
2. Attach the DC terminal covers.
3. Route the DC cables from the battery—with the cables not connected to the
battery—and connect them to the Xantrex XW Power Distribution Panel:
negative to negative bus, positive to the input end of the DC breaker.
To properly attach and torque the positive cable to the DC breaker, you may
need to temporarily remove the breaker from the rail.
4. Perform the procedures in “Making AC Connections” before connecting the
DC cables from the Xantrex XW Power Distribution Panel to the battery.
WARNING: Shock Hazard
Ensure that all AC and DC breakers are switched OFF before connecting or
disconnecting the battery cables and that all sources of power (both AC and DC)
are disconnected from the inverter.
Figure 2-11 Xantrex XW Inverter/Charger DC Connections
Bottom View
Negative (–, black)
battery terminal
Positive (+, red)
battery terminal
BTS port (RJ11)
Chassis Ground
Lug
Battery Temperature
Sensor (included)