Setup
118
Table of parameters for the two illustrations:
Parameters Value
Enable alarms Check this box to send alarm emails. Otherwise the configured emails
will not be sent but the registers will still be scanned.
Period alarms Scanning period in milliseconds for the configured register values.
Slave Address of the Modbus slave.
Type Bit for word bit or Word for a complete word.
Register Address of register.
Bit Accessible if Bit is selected as type, this field indicates the word bit
number.
Operator Trigger operation:
l for words: None (no alarm to trigger), <, <=, >, >=, =, <>, bad (for
exceptions and timeouts on request).
l for word bits: None (no alarm to trigger), RE (rising edge), FE (falling
edge), bad (for exceptions and timeouts on request).
Value Setpoint, decimal value compared with the current value (Modbus
register).
Email to Destination email address (maximum length 80 characters).
Subject Subject of the email (80 characters maximum).
Text Text part of the email (512 characters maximum).