Services
27
Internal Module
Registers
The TSX ETG 1000 module provides four register zones:
l User zone,
l Command zone
l Diagnostic zone
l Periodic zone
The user zone (registers 0 to 63).
This zone is available for unrestricted use. The user can read or write in this zone
by means of Modbus TCP requests or by RDE/GDE (data table/graphics objects).
This zone can be used in various ways:
l to send a mail from an Ethernet network
l to send a mail without a Modbus device: test email
l to store device values or to exchange values between devices
l to simulate a Modbus device,
l etc.
The command zone (register 500 to 511):
Register Description
500 Command status for register 501:
l = 0 for command not OK
l = FFFF for command in progress
l <> 0 for command not OK
501 Command:
l = 0 no command
l = 1 for alarm test service
l = 2 for open PPP connection
l = 3 for close PPP connection
502 Register 501 = 1 then number of alarm to be tested
502 to 505 Register 501 = 2 or 3 and IP address = 86.16.0.4 (for example)
l Register 502 = 86 for the 1st value of the IP address
l Register 503 = 16 for the 2nd value of the IP address
l Register 504 = 0 for the 3rd value of the IP address
l Register 505 = 4 for the 4th value of the IP address
506 to 511 Reserved.
Note: a new command is not authorized if the status value (register 500) is FFFF.
The command parameters for register 502 to 505 must be entered before the
command (register 501).